Valve Wire Sizing (Maximum One-Way Distance in Feet Between Controller and Valve) | |||||||
---|---|---|---|---|---|---|---|
Ground Wire Size | Control Wire (mm²) | ||||||
Below is a chart indicating the maximum wire runs that can be used when installing Hunter AC solenoids and valves. | |||||||
1.0 mm² | 1.2 mm² | 1.6 mm² | 2.0 mm² | 2.5 mm² | 3 mm² | 4 mm² | |
1.0 mm² | 259 | 317 | 369 | 411 | 445 | 469 | 485 |
1.2 mm² | 317 | 408 | 503 | 585 | 655 | 710 | 744 |
1.6 mm² | 369 | 503 | 655 | 802 | 939 | 1052 | 1128 |
2.0 mm² | 411 | 585 | 802 | 1033 | 1271 | 1487 | 1646 |
2.5 mm² | 445 | 655 | 939 | 1271 | 1646 | 2033 | 2344 |
3 mm² | 469 | 710 | 1052 | 1487 | 2033 | 2652 | 3210 |
4 mm² | 485 | 744 | 1128 | 1646 | 2344 | 3210 | 4063 |
ري المسطحات الخضراء