The Hunter NODE and WVC battery powered controllers can have the valve installed a maximum of 100 feet (30 m) away.
XC Hybrid Wire Sizing Chart
Below is a chart indicating maximum wire lengths when using a Hunter DC latching solenoid combined with a Hunter XC Hybrid controller.
WIRE SIZE |
MAXIMUM DISTANCE* |
|
---|---|---|
|
FEET |
METERS |
18 AWG / 0.8 mm2 |
550 |
168 |
16 AWG / 1.3 mm2 |
870 |
265 |
14 AWG / 2.1 mm2 |
1380 |
421 |
12 AWG / 3.3 mm2 |
2200 |
671 |
* Using Hunter DC Latching Solenoids |