WFS - Example of Install

Legend:

Hunter Wireless Flow Sensor and transmitter (WFS)

  1. Irrigation valve box per plan heat stamp lid with “FS” in Letters

  2. Finished grade in turf

  3. Adjacent turf (per plan)

  4. Adjacent mulch (per plan)

  5. Finished grade in planter bed

  6. Brick supports (4)

  7. Filter fabric-wrap twice around brick supports

  8. 3/4" washed gravel-4" min. depth

  9. Irrigation lateral

  10. Mainline to zone valves

  11. Sensor wire: Approximately 32” long. DO NOT cut or extend wire.

NOTE: Contractor to cut 3-1/4" dia. hole through valve box lid.

INSTALLATION DIAGRAM

  1. Minimum 10x pipe diameter from nearest turn in system
  2. MAIN LINE OR LATERAL LINE
  3. WATER FLOW
  4. Minimum 5x pipe diameter from nearest turn in system

INSTALLING THE FLOW-SYNC SENSOR AND FCT TEE

*Note: Not to scale