X2 - Connecting Valves

Installation of the X2 should only be done by trained personnel. Please refer to the example and instructions below for connecting the controller to the valve.

  1. Route valve wires between the control valve location and controller.
  2. At valves, attach a common wire to either solenoid wire on all valves. This is most commonly a white-colored wire. Attach a separate control wire to the remaining wire of each valve. All wire connections should be done using waterproof connectors.
  3. Secure the white valve common wire to the C (Common) screw on the terminal strip. Attach each of the individual valve control wires to the appropriate station terminals and tighten their screws.
  4. The transformer wires are already connected to the AC terminals so all that is required is to connect the primary power outlet for the plug.

NOTE: The MV terminal is only to be used if a master valve is on the system. Learn more

 

 

Wire Distance

Valve Wire Sizing (Maximum One-Way Distance in Feet Between Controller and Valve)
Ground Wire SizeControl Wire (ft)

 

 

Below is a chart indicating the maximum wire runs that can be used when installing Hunter AC solenoids and valves.

 
18 AWG
16 AWG
14 AWG
12 AWG
10 AWG
8 AWG
6 AWG
18 AWG
850
1040
1210
1350
1460
1540
1590
16 AWG
1040
1340
1650
1920
2150
2330
2440
14 AWG
1210
1650
2150
2630
3080
3450
3700
12 AWG
1350
1920
2630
3390
4170
4880
5400
10 AWG
1460
2150
3080
4170
5400
6670
7690
8 AWG 
1540
2330
3450
4880
6670
8700
10530
6 AWG
1590
2440
3700
5400
7690
10530
13330