These tables are designed for quick reference and are set up to provide maximum wire runs, given the information at the bottom of the table. Maximum one-way distance in feet between controller and valve heavy-duty solenoid: 24 VAC, 350 mA inrush current, 190 mA holding current, 60 Hz; 370 mA inrush current, 210 mA holding current, 50 Hz. The tables represent a single active solenoid. The wire distances should be halved with two solenoids operating simultaneously on the same wires.
Wire Distance (mm²)
Ground (C) Wire | Control (Hot) Wire (mm²) | |||||
---|---|---|---|---|---|---|
0.5 mm² | 1.0 mm² | 1.5 mm² | 2.5 mm² | 4.0 mm² | 6.0 mm² | |
0.5 mm² | 140 | 190 | 210 | 235 | 250 | 260 |
1.0 mm² | 190 | 290 | 335 | 415 | 465 | 495 |
1.5 mm² | 208 | 335 | 397 | 515 | 595 | 647 |
2.5 mm² | 235 | 415 | 515 | 730 | 900 | 1030 |
4.0 mm² | 250 | 465 | 595 | 900 | 1175 | 1405 |
6.0 mm² | 260 | 495 | 647 | 1030 | 1405 | 1745 |