Operating Specifications
Temperature | Pressures | Humidity |
---|---|---|
0 to 140ºF/60ºC | up to 200 psi/13.7 bar | up to 100% |
Flow Range
Flow-Sync Sensor Diameter |
Operating Range (Gpm) | |
---|---|---|
Minimum* | Suggested Maximum** | |
1" | 2 | 17 |
1½" | 5 | 35 |
2" | 10 | 55 |
3" | 28 | 120 |
4" | 34 | 195 |
* Minimum recommended flow for accurate flow readings
** Good design practice dictates the maximum flow not to exceed 5ft/sec. Suggested maximum flow is based upon Class 200 IPS plastic pipe
Maximum Distance Between Controller/Sensor Decoder and Sensor: 1000 ft/300 m
Wire: 18 AWG/1 mm, 36”/1 m leads (Ø = diameter)
Dimensions
FCT Tee Fitting | Height | Width | Length | Straight Pipe upstream (Ø x 10) |
Straight Pipe downstream (Ø x 5) |
---|---|---|---|---|---|
FCT 100 | 4.8"/12 cm | 2.3"/6 cm | 4.5"/11 cm | 10"/25 cm | 5"/13 cm |
FCT 150 | 5.4"/14 cm | 2.3"/6 cm | 4.6"/12 cm | 15"/38 cm | 8"/20 cm |
FCT 158 | 5.4"/14 cm | 2.3"/6 cm | 5.1"/13 cm | ||
FCT 200 | 6″/15 cm | 2.7"/7 cm | 4.7"/14 cm | 20"/50 cm | 10"/25 cm |
FCT 208 | 6"/15 cm | 2.7"/7 cm | 5.4"/14 cm | ||
FCT 300 | 7"/18 cm | 4"/10 cm | 6.2"/16 cm | 30"/76 cm | 15"/38 cm |
FCT 308 | 7"/18 cm | 4.2"/11 cm | 6.4"/16 cm | ||
FCT 400 | 8"/20 cm | 5"/13 cm | 6.2"/16 cm | 40"/1 m | 20"/50 cm |
Flow-Sync Calibration Factors
Hunter controllers allow selection of the correct pipe size by FCT model number. No further calibration is needed.
If “Other” is selected, K-factor and Offset information may be entered directly. Following are K-factor and Offset values for best results with each available FCT model.
Flow Sensor Values
Hunter Flow Sensor | K-Factor | Offset |
---|---|---|
HFSFCT100 | 0.44 | 0.39 |
HFSFCT150 | 1.13 | 0.00 |
HFSFCT158 | 0.92 | 1.22 |
HFSFCT200 | 2.13 | 0.23 |
HFSFCT208 | 1.72 | 1.70 |
HFSFCT300 | 4.61 | 0.18 |
HFSFCT308 | 5.87 | 1.07 |
HFSFCT400 | 8.77 | 0.48 |