These tables are designed for quick reference and are set up to provide maximum wire runs, given the information at the bottom of the table. Maximum one-way distance in feet between controller and valve heavy-duty solenoid: 24 VAC, 350 mA inrush current, 190 mA holding current, 60 Hz; 370 mA inrush current, 210 mA holding current, 50 Hz. The tables represent a single active solenoid. The wire distances should be halved with two solenoids operating simultaneously on the same wires.
Wire Distance (ft)
Ground Wire | Control Wire (ft) | |||||
---|---|---|---|---|---|---|
18 AWG | 16 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG | |
18 AWG | 850 | 1040 | 1210 | 1350 | 1460 | 1540 |
16 AWG | 1040 | 1340 | 1650 | 1920 | 2150 | 2330 |
14 AWG | 1210 | 1650 | 2150 | 2630 | 3080 | 3450 |
12 AWG | 1350 | 1920 | 2630 | 3390 | 4170 | 4880 |
10 AWG | 1460 | 2150 | 3080 | 4170 | 5400 | 6670 |
8 AWG | 1540 | 2330 | 3450 | 4880 | 6670 | 8700 |