Valves - Wire Distance

These tables are designed for quick reference and are set up to provide maximum wire runs, given the information at the bottom of the table. Maximum one-way distance in feet between controller and valve heavy-duty solenoid: 24 VAC, 350 mA inrush current, 190 mA holding current, 60 Hz; 370 mA inrush current, 210 mA holding current, 50 Hz. The tables represent a single active solenoid. The wire distances should be halved with two solenoids operating simultaneously on the same wires.

Wire Distance (ft)

 

Ground WireControl Wire (ft)
 
18 AWG
16 AWG
14 AWG
12 AWG
10 AWG
8 AWG
18 AWG
850
1040
1210
1350
1460
1540
16 AWG
1040
1340
1650
1920
2150
2330
14 AWG
1210
1650
2150
2630
3080
3450
12 AWG
1350
1920
2630
3390
4170
4880
10 AWG
1460
2150
3080
4170
5400
6670
8 AWG
1540
2330
3450
4880
6670
8700

 